SENSAiO
Differential Pressure (ΔP)
Wireless differential pressure sensor
Ex-rated ΔP sensor with two synchronised pressure inputs - detects clogging of filters, heat exchangers, separators and manifolds over LoRaWAN.
Price and availability on requestAdd one or several devices to your request - we will send a quote with lead times.
Official supply & warranty
Setup & deployment
Support in Kazakhstan
Technical specifications
Measurement
- Principle
- piezoresistive, two synchronised inputs
- Range
- ±1 kPa … ±4 MPa
- Accuracy
- 0.20 % FS up to 40 kPa · 0.16 % up to 400 kPa · 0.20 % up to 4 MPa
- Process connection
- 1/2" NPT/NPTF, G1/2", DIN 19213, IEC 61518
- Materials
- 316L or Inconel 625 · aluminium or 316L housing
- Applications
- filters, heat exchangers, separators, manifolds, HVAC
Ex protection
- ATEX
- II 1 GD · I M1 (Ex ia I Ma) · UKCA
- IECEx
- Ex ia IIC T4 Ga · Ex ia IIIB T135 °C Da
- NEC (North America)
- Class I/II/III, Groups A-G, T4
- Use
- Zones 0/1/2 and 20/21/22, M1 mining - per the certificate of the specific version
LoRaWAN radio
- Protocol
- LoRaWAN Class A · OTAA · ADR
- Range
- up to 10 km line of sight
- Frequency plans
- EU863-870, RU864-870, IN865-867, US902-928, AU915-928, AS923, KR920-923
- RF power
- up to 14 dBm ERP
- Security
- AES-128, dedicated secure element
- Reporting
- 100 frames/day by default, configurable; local buffering during outages
Housing & power
- Power
- Li-MnO2 3.0 V, 12.4 Ah, field-replaceable D-size battery
- Battery life
- up to 10 years (at 15-minute reporting)
- Ingress protection
- IP65 / IP67
- Operating temperature
- −40 … +70 °C
- Vibration / shock
- 20 g (5-2000 Hz) · shock up to 100 g / 6 ms
- Conformity
- ATEX, RED, PED, RoHS, IEC 61010-1
Manufacturer data: www.sensa.io · current datasheets and certificates on request